Siemens APOGEE™ FLN (P1) Communication Kit
3-2
For more information visit:
www.EatonElectrical.com
MN04008002E
February 2006
4. Strip the communication cables so they can be secured to the drive frame with the
grounding clamp. See
Figure 3-3
.
Figure 3-3: Grounding the Communication Cables
Grounding Only One Point on the Net
In this method of grounding, the shield is connected to ground only at the last device on the
network. Other devices on the network bypass the shield.
1. Strip about 2 in. (5 cm) from the cables and cut off the gray cable shield.
2. Leave no more than 1/4 in. (1 cm) of each cable outside the terminal block, and strip the
ends of both cables to about 0.2 in. (0.5 cm) to fit in the terminals. See
Figure 3-4
.
Note:
We recommend that you use an Abico connector to fit the shields into the terminal.
Figure 3-4: Stripping the Communication Cables
A
B
3
4
5
2
1
Shield