Setting, Unsetting, and Restoring the System
13
Siemens Building Technologies
Fire Safety & Security Products 09.2008
5.5 Force Setting the System
The system can be forced to set while an alarm
zone is still open. This operation inhibits the open
zone and sets the system as normal.
If a user has the right to FORCE SET the system
and an alarm zone is open, when the FULLSET or
PARTSET option is selected, the Keypad buzzer
beeps and the first line of the display indicates the
open zone. The user is presented with the options
to QUIT (left soft key) or FORCE (right soft key).
QUIT: Selecting this option aborts the attempt to
set the system and returns the user to User
Programming.
FORCE: Selecting this option inhibits the open
zone and forces the system to set.
5.6 Unsetting the System
To UNSET a system:
1. Enter a valid user code. The Keypad displays
a prompt to unset the system.
2. To UNSET the system, press SELECT (right
soft key). The Keypad display indicates that
the system is unset on the bottom line of the
display for approximately 5 seconds. After this
time has elapsed, the bottom line is cleared.
3. If the alarm has been activated, entering the
user code silences all bells and strobes and
the message PANEL DISARMED is displayed
on the Keypad for approximately 5 seconds.
4. The source of the alarm condition is displayed
on the Keypad and the Alert LED flashes. The
Keypad continues to display the alert until the
alert is restored.
...UNSET?...
EXIT SELECT
SYSTEM UNSET
PANEL DISARMED
ALARM ZONE 2
FIRST ZONE
ZONE 1 OPEN
QUIT FORCE
…FORCED SET?...
BACK SELECT
18/06/2008 12:30
SETTING 45 SECONDS
10/06/2008 12:30
SYSTEM FULLSET