Product Characteristics
4.2 Installation
SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
Operating Instructions, 01/2013, C79000-G8976-C270-03
25
Mode electrical channel without segment monitoring
CH1 is set to this mode, when S0 is in position 1.
Note: This mode should only be set in the star segment of the star topology.
4.2.3.4 Setting the mode of the electrical channel (CH0)
Only for OLM / P22 and OLM / G22
Mode electrical channel with segment monitoring
CH0 is set to this mode, when S8 is in position 0.
Mode electrical channel without segment monitoring
CH0 is set to this mode, when S8 is in position 1.
Note: This mode should only be set in the star segment of the star topology.
4.2.3.5 Setting the mode of the optical channels (CH2, CH3)
The mode can be set separately for each optical channel. Combinations of the modes bus
with and bus without fiber-optic link monitoring are possible. Remember that the two optical
channels connected via the fiber-optic cables must always be set to the same mode! When
operating with devices that do not provide fiber-optic link monitoring this mode cannot be
used and must be disabled on the OLM V4.
If mode redundant optical ring is used, both optical channels have to be set to this mode
accordingly.
Mode bus with fiber-optic link monitoring and segmentation
CH2 is set to this mode, when S1 and S2 are in position 0.
CH3 is set to this mode, when S3 and S4 are in position 0.
Mode bus without fiber-optic link monitoring
CH2 is set to this mode, when S1 is in position 1 and S2 is in position 0.
CH3 is set to this mode, when S3 is in position 1 and S4 is in position 0.
Mode redundant optical ring
CH2 is set to this mode, when S1 and S2 are in position 1.
CH3 is set to this mode, when S3 and S4 are in position 1.
Note: Remember that both optical channels of a module must be set to the same mode.