SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
Operating Instructions, 01/2013, C79000-G8976-C270-03
17
4 Product Characteristics
4
4.1 Technical Specifications
Characteristics Device type
OLM P11 V4.0
OLM P12 V4.0
OLM P22 V4.0
OLM G11 V4.0
OLM G12 V4.0
OLM G22 V4.0
OLM G12-EEC V4.0
OLM G11-1300 V4.0
OLM G12-1300 V4.0
Power supply
Operating voltage 24 V DC safety extra low voltage
permitted voltage range 18..32 V DC NEC Class 2
Current consumption max. 200 mA
Output voltage for bus termination
RS-485 (D-sub jack, pin 6)
5 V DC+5/-10%,
Signaling Contact
Function floating contact, opens in case of error
Voltage CE: max. 50 V DC/30 V AC safety extra low voltage
cULus: max. 30 V DC/30 V AC safety extra low voltage
Current max 1.0 A
Signal transmission
Transmission rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 Kbps
1.5; 3; 6; 12 Mbps
Transmission rate setting automatic
Bit error rate
<10
-9
Signal delay time (any input/output) 6.5 t
Bit
Retimer
Input (all channels)
Signal distortion
Bit length
± 30%
± 0.12%
Output (all channels)
Average bit length
± 0.01%
Status signaling
Device LED system, red/green together with signaling contact
Electrical channel LED yellow/red
Optical channels LED yellow/red
Optical level level display with green/yellow/red LED