Notes on configuration and operation
6.7 Media redundancy
CP 343-1
Manual, 10/2012, C79000−G8976−C201-07
47
6.6.3 Configured S7 connections cannot be operated if the IP address is assigned
over DHCP
Note
If you obtain the IP address using DHCP, any S7 connections you may have configured will
not work. Reason: The configured IP address is replaced during operation by the address
obtained with DHCP.
6.6.4 IP access protection using the IP access control list with a PROFINET IO
device
Note the following behavior if IP access protection is activated:
If the CP is configured as a PROFINET IO device, you will need to enter the IP address of
the PROFINET IO controller in the IP access control list.
With programmed communications connections, you should also note the following section:
IP access protection with programm
ed communication connections (Page 51)
6.7 Media redundancy
You can use the CP in a ring topology with media redundancy. The CP can only be a
redundancy client.
For more detailed information on configuration, refer to the online help of the "Media
redundancy" tab and Part A of the manual, see /1/ (Page 68).
6.8 Timeofday synchronization
General rules
The CP supports the two modes explained below for timeofday synchronization:
SIMATIC mode
NTP mode (NTP: Network Time Protocol)
No automatic changeover to daylight saving time is defined in NTP. As a result, you may
need to implement this changeover using a program application.
Project engineering
For more detailed information on configuration, refer to the online help of the "Time-of-day
synchronization" parameter group and in Part A of the manual /1/ (Page 68).