Additional components
for expansion with …
The AS-Interface functions without any
problem with standard components up
to a length of 500 m – without re-
peaters or extenders up to 100 m.
… repeaters
When using repeaters, up to two re-
peaters can be connected in series, on
which all components can be distrib-
uted to the segments in any way. But
there is a widespread misunderstand-
ing that an AS-Interface network therefore
has a maximum extent of 300 meters!
Much larger extents are possible because
parallel arrangement of several lines in a
star configuration is possible. In a mail sort-
ing system, an AS-Interface network has a
total extent of 1600 meters. The repeater
works as an amplifier. The slaves can be
connected to all AS-Interface segments.
Each segment requires a separate power
supply unit. In addition, the repeater iso-
lates the two segments, which improves
selectivity in the event of a short-circuit.
Master
Segment
max. 100 m
Segment
max. 100 m
Repeater
Power
supply
unit
SlavePower
supply
unit
Slave
Repeater
Segment
max. 100 m