Power supply units
AS-Interface power supply units are a
necessity of an AS-Interface network.
They produce a controlled DC voltage of
30 V DC with a high degree of stability
and low residual ripple and work on the
principle of a primary switched-mode
regulator.
Data and power are always transmitted
simultaneously via the AS-Interface
AS-Interface
power supply unit
twisted-pair cable. For that reason, the
AS-Interface power supply units ensure
not only the power supply to the AS-In-
terface power supply unit but also data
decoupling.
That is why no standard power supply
units must ever be used to power an
AS-Interface network.
AS-Interface power supply units supply
the electronics of the network (AS-In-
terface master, AS-Interface modules)
and all connected sensors. Depending
on the power requirement of the AS-In-
terface network, a range of power sup-
ply units graded from 2.4 to 7 A are
available.
The power for the actuators (outputs) is
usually not taken from the AS-Interface
cable but from a separate power supply
that is connected to the slaves by
means of a separate cable (e.g. black
AS-Interface profiled cable). In this way,
it is also possible to implement EMERG.
STOP circuits for local and remote iso-
lation. For cases in which an auxiliary
power supply is required in addition to
the AS-Interface power, the very com-
pact 1 x 30 V DC and 1 x 24 V DC com-
bined power supply unit can be used.
For the power supply to the output cir-
cuits an external additional 20 to 30 V
DC power source (AUX POWER) is re-
quired. The additional power source
must conform to VDE 0106 (PELV), pro-
tection class 111.