Siemens SITRANS P Manual de usuario Pagina 169

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 222
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 168
UMSITRAPDS3-1 Model Designations and Specifications
November 2010
9-11
Measuring cell filling Silicone oil or inert filling liquid; max. 160 bar a (2320 psia) with oxygen
measurement
Process connection Connection shank G1/2A to DIN EN837-1, female thread 1/2-14 NPT or oval flange
to DIN 19213 with mounting thread M10 or 7/16-20 UNF to EN 16518
Power Supply U
H
Terminal voltage at transmitter 10.5 to 45 Vdc
10.5 to 30 Vdc in intrinsically-safe mode
Certificate and approvals
See Table 9-20
HART communication
HART communication 230 to 1100
Protocol HART Version 5.x
Software for computer SIMATIC PDM
Note: 3.6 psi absolute (250 mbar a) Capsule
This measuring cell is designed for operation within the measuring limits of 0 to 3.63 psi
(absolute). When stored in the normal ambient pressure of about of about 14.7 psi
(absolute), the measuring cell is in the overload state. An overload error of up to 0.03 psi
may occur. The overload disappears in normal operation within the measuring limits and
the transmitter operates within specifications.
When performing accurate continuous pressure measurements within the measuring
limits, a readjustment of the transmitter zero for absolute pressure must be performed
after approximately one day (refer to Section 6.2.5).
If pressure measurements exceed the measuring limits repeatedly (e.g. batch processes
with transitions between vacuum and ventilation), a measuring cell with a maximum
range of 18.9 psi should be selected to avoid overloading.
Vista de pagina 168
1 2 ... 164 165 166 167 168 169 170 171 172 173 174 ... 221 222

Comentarios a estos manuales

Sin comentarios