Overview
SITRANS LU SAM Satellite Alarm Module provides up to 20 relay
outputs for the measurement points of the SITRANS LU10 level
monitor.
■
Benefits
• The SITRANS LU SAM can be located up to 1500 m (5000 ft)
from the SITRANS LU10
• Relay outputs can be assigned to any point on the
SITRANS LU10
■
Application
The operation of the SITRANS LU SAM is programmed via the
SITRANS LU10. The only on-board settings are for bank selec-
tion and output testing.
Using a SITRANS LU SAM, you can have two relay outputs for all
ten measurement points, all 20 for a single measurement point
or any combination between the two.
All relays are Form C to allow NO or NC wiring.
■
Technical specifications
C) Subject to export regulations AL: N, ECCN: EAR99
Mode of operation Satellite alarm module
Input
Communications Data from SITRANS LU10
• Transmission rate
4800 bits/s
• Voltage
± 20 mA bipolar current loop
Output
Relays 20 multi-purpose relays, program-
mable from SITRANS LU10
SPDT Form C relays, rated 5 A at
250 V AC, resistive load
± 20 mA bipolar current loop
Input and transmission
• Max. load
1 receiving unit
Rated operation conditions
Ambient conditions
• Ambient temperature -20 ... +50 °C (-5 ... +122 °F)
• Location Indoor/outdoor
• Installation category
II
• Pollution degree
4
Design
Weight 3 kg (6.6 lbs)
Material (enclosure)
Polycarbonate
Degree of protection Type 4X/NEMA 4X/IP65
Cable connection
2 copper conductors, twisted,
with foil shield/drain wire, 300 V
0.5 ... 0.75 mm² (22 ... 18 AWG)
Electrical connection and relay con-
nection
Copper conductor according to
local requirements,
rated 250 V 5 A
Power supply
100/115/200/230 V AC ± 15 %,
50/60 Hz, 20 VA
Displays and controls
1 LED for display of voltage/com-
munications state, 20 LEDs for
display of relay states
Certificates and approvals
CE, FM, CSA
US/C,
C-TICK
Selection and Ordering data
Order No.
SITRANS LU SAM
Satellite alarm module provides up to 20 relay
outputs for the measurement points of the
SITRANS LU10 level monitor.
Approvals: CSA
US/C
, FM, CE, C-TICK
C)
7ML5811-1A
Operating Instructions
English
C)
7ML1998-5CF02
German
Note: Instruction manuals should be ordered as a
separate line item on the order.
C)
7ML1998-5CF32
This device is shipped with the Siemens Milltronics
manual CD containing the complete Quick Start and
instruction manual library.
Comentarios a estos manuales