Level Measurement
Continuous level measurement - Ultrasonic controllers
SITRANS LU10
5/163
Siemens FI 01 · 2011
5
Dimensional drawings
SITRANS LU10, dimensions in mm (inch)
Schematics
SITRANS LU10 connections
Mounting hole
4.3 (0.17) diameter
access under lid
(4 places)
Suitable location for conduit entrances. Use water-
tight conduit hubs to maintain enclosure rating.
267 (10.5)
92
(3.6)
106
(4.2)
285 (11.2)
209 (8.2)
172 (6.8)
3 41 2
7 8
0
6
P P
C
9
5
mA
%
10SITRANS LU
1
%
0
100
2 3 4 5 6 7 8 9 10
Position SW1
for 100/115/
200/230 V
AC
Operation
(50/60 Hz,
15 VA)
Peripheral
communication
Note 3
Note 2Note 1
To transducers (10 max.) RG62-A/U
coax, 365 m / transducer max.
transducers
Notes:
1. Transducer cables must be run in a grounded metal conduit separate from other wiring (except TS-3 temperature sensor wiring, if
applicable).
2. Optional TIB-9 card for multiple temperature sensors. Do not jump the terminals if TS-3s are not used.
3. The SITRANS LU10 is compatible with the following Siemens Milltronics peripherals:
- SITRANS LU SAM - relay satellite alarm module
- SITRANS LU AO - analog output module
Temp.
sensor
white/shield
black
white/shield
black
white/shield
black
white/shield
black
white/shield
black
white/shield
black
white/shield
black
white/shield
black
white/shield
black
V
P12
SYNC
L2/N L1
TX RX
41 42 43 44 45 46 47 48 49 50 51 521 2
1 2 9 10
3 4 18 19 20 21 22 23 24
2
2
3 9 10
3 9 10
25 26 36 37 38 39 40
1 2 1 2
© Siemens AG 2010