Digital Modules
4-46
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 421; DI 16 24/60 VUC
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 600 g
Data for Specific Module
Number of inputs 16
Length of cable
• Unshielded
input delay
– 0.5 ms
– 3 ms
– 10 / 20 ms
Max. 100 m
Max. 600 m
Max. 600 m
• Shielded line length 1000 m
Voltages, Currents, Potentials
Number of inputs that can be
triggered simultaneously
16
Isolation
• Between channels and
backplane bus
Yes
• Between the channels Yes
– In groups of 1
Permitted potential difference
• Between the different
circuits
75 VDC, 60 VAC
Insulation tested with
• Channels against
backplane bus and load
voltage L+
1500 VAC
• Channels among one
another
1500 VAC
Current consumption
• From the backplane bus Max.150 mA
Power dissipation of the
module
Typ. 8 W
Status, Interrupts, Diagnostics
Status display Green LED per
channel
Interrupts
• Hardware interrupt
• Diagnostic Interrupt
Parameters can be
assigned
Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
• Group error display
– For internal fault Red LED (INTF)
– For external fault Red LED (EXTF)
• Channel error display (F) None
• Diagnostic information can
be displayed
Possible
Monitoring for
• Wire break I > 0.7 mA
Substitute value can be applied No
Sensor Selection Data
Input voltage
• Rated value 24 VUC to 60 VUC
• For signal “1” 15 to 72 VDC
-15 VDC to -72 VDC
15 to 60 VAC
• For signal “0” -6 VDC to +6 VDC
0 VAC to 5 VAC
Frequency range 47 DC/AC to 63 Hz
Input current
• At signal “1” Typ. 4 mA to 10 mA
Input characteristic curve Similar to IEC 61131
1)
Connection of two-wire BEROs
• Permitted bias current
Possible
Max. 0.5 mA to 2 mA
2)
Time, Frequency
Internal preparation time for
• Only hardware interrupt
enable
Max. 450 s
• Enable hardware and
diagnostic interrupts
Max. 2 ms
Input delay
• Parameters can be
assigned
Yes
• Rated value 0.5/3/10/20 ms
Values go into cycle and response times.
Sensor Circuit
Resistance circuit of the sensor
for wire break monitoring
• Rated voltage 24 V
(15 V to 35 V)
• Rated voltage 48 V
(30 V to 60 V)
• Rated voltage 60 V
(50 V to 72V)
18 kΩ
39 kΩ
56 kΩ
1
) IEC 61131 does not specify any data for UC
modules. The values have been adapted as much
as possible to IEC 61131.
2)
Minimum closed-circuit current is required for wire
break monitoring.