Digital Modules
4-46
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 421; DI 16 24/60 VUC
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 600 g
Data for Specific Module
Number of inputs 16
Length of cable
Unshielded
input delay
0.5 ms
3 ms
10 / 20 ms
Max. 100 m
Max. 600 m
Max. 600 m
Shielded line length 1000 m
Voltages, Currents, Potentials
Number of inputs that can be
triggered simultaneously
16
Isolation
Between channels and
backplane bus
Yes
Between the channels Yes
In groups of 1
Permitted potential difference
Between the different
circuits
75 VDC, 60 VAC
Insulation tested with
Channels against
backplane bus and load
voltage L+
1500 VAC
Channels among one
another
1500 VAC
Current consumption
From the backplane bus Max.150 mA
Power dissipation of the
module
Typ. 8 W
Status, Interrupts, Diagnostics
Status display Green LED per
channel
Interrupts
Hardware interrupt
Diagnostic Interrupt
Parameters can be
assigned
Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
Group error display
For internal fault Red LED (INTF)
For external fault Red LED (EXTF)
Channel error display (F) None
Diagnostic information can
be displayed
Possible
Monitoring for
Wire break I > 0.7 mA
Substitute value can be applied No
Sensor Selection Data
Input voltage
Rated value 24 VUC to 60 VUC
For signal “1” 15 to 72 VDC
-15 VDC to -72 VDC
15 to 60 VAC
For signal “0” -6 VDC to +6 VDC
0 VAC to 5 VAC
Frequency range 47 DC/AC to 63 Hz
Input current
At signal “1” Typ. 4 mA to 10 mA
Input characteristic curve Similar to IEC 61131
1)
Connection of two-wire BEROs
Permitted bias current
Possible
Max. 0.5 mA to 2 mA
2)
Time, Frequency
Internal preparation time for
Only hardware interrupt
enable
Max. 450 s
Enable hardware and
diagnostic interrupts
Max. 2 ms
Input delay
Parameters can be
assigned
Yes
Rated value 0.5/3/10/20 ms
Values go into cycle and response times.
Sensor Circuit
Resistance circuit of the sensor
for wire break monitoring
Rated voltage 24 V
(15 V to 35 V)
Rated voltage 48 V
(30 V to 60 V)
Rated voltage 60 V
(50 V to 72V)
18 k
39 k
56 k
1
) IEC 61131 does not specify any data for UC
modules. The values have been adapted as much
as possible to IEC 61131.
2)
Minimum closed-circuit current is required for wire
break monitoring.