SIMATIC customers have free use of the application tips. These tips are only a general approach to using SIMATIC with various applications. Your
specific application may be different. It is your responsibility to use SIMATIC properly in your applications.
Step 24 – Configure Remote access
Select “Yes” to enable HTTPS remote access, change the Port to 4443 in case you want to use
Port 443 to allow restricted logon access to the PLC. You will also need to add a firewall rule to
allow a connection “From IP address”. This IP address can be a specific address or if you leave
it as “0.0.0.0/0” then anyone can try and access it. This is why a secure password is critical. I
would suggest that you enter the IP address that is assigned to your location to keep others from
gaining access or do not enable remote access. To test the connection the computer must have
internet access, using Internet Explorer or Mozilla Firefox, enter for example
https://192.168.44.44:4443 or https://m875demo.dyndns.org:4443 and you should get to the
login screen.
Step 25 – Configure Firewall Rules
By default the Firewall is configured to block everything.
The firewall is configured to accept only TCP data incomming to our PLC (192.168.10.2) on Port
80 (Webserver) and Port 102 (Simatic Data).