1.0 INTRODUCTION
This manual describes the installation, operation, and maintenance of Model Series 77 Electric-to-Pneumatic
Transducers. These transducers are FM approved for installation in various National Electrical Code classified
hazardous locations. Note that particular attention must be given to the installation and maintenance of the 77F
models (see Model Designation below). These models are FM approved to be part of an intrinsically safe system
when installed and maintained according to the requirements outlined in this manual and in the installation
instructions provided by the energy limiting barrier manufacturer.
IMPORTANT
Save this Instruction and make it available for installation and maintenance of the
transducer.
The Model Series 77 E/P Transducer provides a 3 to 15 psig output that is proportional to a DC milliamp input.
Several input ranges are available as is an optional 3-27 psig output range (see Model Designation below). Other
options include: a tapped exhaust provision, 0 to 4 mA factory calibration, and reverse acting output. Each
transducer has a plate that states model designation and applicable certifications. See Figure 1-1 for a sample
nameplate
1.1 MODEL DESIGNATION
Sample Model Number 77 E 3 F N
E/P Transducer
Exhaust
Exhaust Top Housing Boosted
-- Atmosphere Aluminum No
E Tapped Aluminum No
B Atmosphere Aluminum Yes
S Atmosphere Stainless Steel No
T Tapped Stainless Steel No
Input/Output
Model No.
Entry
Input Range
(mAdc)
Output Range
(psig)
Input Impedance
(Ohms)
3 1-5 3-15 2450
3A 0-4 3-15 2450
8 4-20 3-27 610
16 4-20 3-15 185
40 10-50 3-15 30
Intrinsic Safety Electrical Classification
F = Intrinsically Safe
- Omit for all other electrical classifications
- Not available with Option R below
- Refer to Section 1.3 for ATEX installations
Options
R = Reverse acting output (e.g. 4 mA = 15 psig; 20 mA = 3 psig)
Note: Option R is not available on Series 77F
6