5.3 TROUBLSHOOTING
Refer to the trouble analysis table below when troubleshooting the transducer. A transducer input signal must be
present and the signal source must be functioning and accurately calibrated. Each darkened area in the table relates a
symptom (top row) to a cause (left-most column).
Symptom
Cause
No Output Output above
full scale and
will not
reduce
Output will
not increase
to full scale
Output will
not decrease
to start of
scale
Output
oscillates
Output erratic
during an input
change (hangs up
and then jumps)
Shipping
screw not in
its Stored
position
Inadequate
or no supply
air
Leak in
output line
or fittings
Input leads
reversed
Inadequate
volume in
output
Transducer
zero out of
adjustment
Transducer
range out of
adjustment
Loose input
leads
Clogged
filter screen
Misaligned
coil
Foreign
object
interfering
with coil
movement
Blocked
exhaust port
Shorted or
open coil
* Loss of
silicon fluid
**Permanent
magnet weak
* Does not occur unless bottom cover has been loosened or removed and maintenance performed.
** Does not occur unless transducer has been dropped or otherwise subjected to a physical shock.