CPU 416F-2, 6ES7416-2FN05-0AB0, Edition 01, as of firmware V5.0.1
4 A5E00981473-02, 11/2006
Probabilities of Failure
Below are the values for the CPU 416F-2 probabilities of failure:
Operation in Low Demand
Mode
low demand mode
(average probability of
failure on demand)
Operation in High Demand
or Continuous Mode
high demand/continuous
mode (probability of a
dangerous failure per hour)
Proof-test interval
F-compatible CPU 416F-2
6ES7416-2FN05-0AB0
4.76E-05 1.09E-09 10 years
Use of the CP 443-5 and the IM 467
If you use one of the following modules as DP Master, you cannot work in the associated line with Distributed Safety. This
means you cannot access modules in such a line from a safety program.
The following modules are affected:
CP 443-5DX00
CP 443-5DX01
IM 467-5GJ00
IM 467-5GJ01