SIMATIC
S7-400
CPU 416F-2, 6ES7416-2FN05-0AB0, Edition 01, as of
firmware V5.0.1
Product Information
Introduction
This Product Information contains important information on 6ES7416-2FN05-0AB0. It is a separate component and should
be considered more up-to-date than the information in the manuals and catalogs if uncertainties arise.
Validity of this Product Information
This Product Information is valid for CPU 416F-2 with order number 6ES7416-2FN05-0AB0, as of hardware release 01 and
as of firmware version V5.0.1.
This Product Information describes the specifications of CPU 416F-2 with order number 6ES7416-2FN05-0AB0 in
comparison to CPU 416-2 with order number 6ES7416-2XN05-0AB0. Information on the CPU 416-2 and the S7-400 is
available in the documentation package 6ES7498-8AA05-8BA0, version 02, which you require in addition to this Product
Information.
Areas of Application
CPU 416F-2 is mainly designed for personal and machine safety and burner controls. In addition to the safety program, you
can also program standard applications.
You want to use the CPU 416F-2 for then you require
Safety-related applications STEP 7 as of version 5.3 + SP2 + HSP110
Optional package S7 Distributed Safety V 5.2 + SP2
Standard applications STEP 7 as of version 5.3 + SP2 + HSP110
Startup protection for inconsistent safety program
The CPU 416F-2 in connection with safety programs which were created with S7 Distributed Safety as of V5.4 SP1,
supports the detection of an inconsistent safety program. This means that the F-CPU detects an inconsistent safety program
in the startup. The F-CPU then goes to Stop and the following diagnostic event is then entered in the diagnostic buffer of the
F-CPU:
"Inconsistent safety program"
No hot restart
The CPU 416F-2 does not support the "hot restart" mode.
Restrictions with SFC 22 "CREAT_DB" and SFC 23 "DEL_DB"
F-DBs can neither be created nor deleted.
Flash Card
If a flash card is inserted, the safety program must be located on the flash card; subsequent loading of fail-safe blocks in the
RAM load memory of the F-CPU is not possible.