20.03.2015 BJJ
Unrestricted © Siemens AG 2015 All rights reserved.
Page 17 Author / Department
Power Modules PM240 / PM240-2
Features
Supply voltage / power range
1AC 200 - 240V +/-10% 0.55 - 4kW/0.75 – 5HP
1
(Low Overload)
0.37 – 3kW/0.5 – 4HP
1
(High Overload)
3AC 200 - 240V +/-10% 0.55 – 7.5kW/0.75 – 10HP
1
(Low Overload)
0.37 – 5.5kW/0.5 – 4.5HP
1
(High Overload)
3AC 380 - 480V +/-10% 0.55 – 250kW/0.75 – 400HP
1
(Low Overload)
0.37 – 200kW/0.5 – 300HP
1
(High Overload)
Overload capability (load cycle, 300 seconds)
Low Overload: 150% for 3 seconds plus 110% for 57 seconds
High Overload ( 75kW): 200% for 3 seconds plus 150% for 57 seconds
High Overload (>75kW): 160% for 3 seconds plus 136% for 57 seconds
Degree of protection IP20/UL open type for cabinet installation
Ambient temperature 0 ... 40
o
C, to 60
o
C with derating
Clock frequency: FSA to FSF (90kW LO) - 4kHz, with derating up to 16kHz
FSF (>90kW LO) - 2kHz, with derating up to 4kHz
Integrated braking chopper to control a braking resistor
Integrated EMC filter up to 90kW LO (Class A filter) to maintain cable-conducted
interference voltages and radiated interference for installations according to EN
61800-3 Category C2
1 Power range from 220 - 240V
Comentarios a estos manuales