Siemens Protection Devices Limited 10
Climatic Tests
50BF Circuit Breaker Fail
Operation Current check - Phase and
Measured Earth with
independent settings
Mechanical Trip
CB Faulty Monitor
Setting Range Is 0.05,0.055…2.0 x In
2 Stage Time Delays Timer 1 20…60000ms
Timer 2 20…60000ms
Operate Level 100% Is, ±5% or ±1%xIn
Disengaging time < 20ms
Operate time following
delay
Tcbf ±1% or ±2ms
Triggered by Any function mapped as trip
contact.
Inhibited by Binary or Virtual Input
Timer By pass Yes, 50BF CB Faulty Input
Temperature
IEC 60068-2-1/2
Operating Range
-10 °C to +55 °C
Storage range
-25 °C to +70 °C
Humidity
IEC 60068-2-3
Operational test
56 days at 40 °C and 95 %
relative humidity
60 Supervision
50 Instantaneous & DTL OC&EF
CT 7SR11 Current
Elements Phase, Derived Earth &
Measured Earth
Number of Elements
2 x 7SR11
4 x 7SR12
2 x OC
2 x Derived EF ‘N’
2 x Measured EF ‘G’
Setting Range Is 0.05,0.06…50 x In
Time Delay 0.00…14400s
Operate Level 100% Is, ±5% or ±1%xIn
Operate time:
50
50N
0 to 2xIs – 35ms, ±10ms,
0 to 5xIs – 25ms, ±10ms
0 to 2xIs – 40ms, ±10ms,
0 to 5xIs – 30ms, ±10ms
Operate time following
delay
Tbasic +td , ±1% or ±10ms
Inhibited by Binary or Virtual Input
64H Restricted Earth Fault
Setting Range 0.05…0.95xIn
Operate Level 100% Is, ±5% or ±1%xIn
Time Delay 0.00… 14400s
Basic Operate Time 0 to 2 xIs 45ms ±10ms
0 to 5 xIs 35ms ±10ms
Inhibited by Binary or Virtual Input
74T/CC Trip/Close Circuit Supervision
Number of supervisable
circuits
3 x Trip and 3 x Close
Number of BI’s Required 1 or 2 per function
51Time Delayed OC&EF (Directional)
CB Maintenance
Elements Phase, Derived Earth &
Measured Earth
Number of Elements
2 x 7SR11
2 x OC
2 x Derived EF ‘N’
2 x Measured EF ‘G’
Characteristic IEC NI,VI,EI,LTI ANSI MI,VI,EI &
DTL
Setting Range Is 0.05,0.1…2.5 x In
Time Multiplier 0.025,0.05…1.6
Time Delay 0,0.01… 20s
Operate Level 105% Is, ±4% or ±1%xIn
Minimum Operate time
IEC
ANSI
Trip Counter Total & Delta
0…10000
Counts to AR Block 0…10000
Frequent Operations 0…10000
I
2
t Alarm 10…100000
Performance
[]
Tm
K
t
I
op
×
=
1
α
Is
[]
TmB
A
t
P
Is
I
op
×
+
=
1
± 5 % absolute or ± 30 ms
Follower Delay 0 - 20s
Reset ANSI decaying, 0 – 60s
Inhibited by Binary or Virtual Input