The relay is housed in a 4U high size E4 case with a
removable clear plastic fascia cover. The plastic fascia
cover can be ordered with or without two push buttons.
to allow the user to view the settings and instruments
without removing the cover.
Two plastic handles are provided to allow the relay to be
withdrawn from its case, contacts in the case ensure that
the CT circuits and normally closed contacts remain short
circuited when the relay is withdrawn.
The rear terminal blocks comprise M4 female terminals
for ring crimp wire connections, to provide a secure and
reliable termination.
Fig 8. Rear view of relay
Construction User Interface
Fig 9. User Interface
The operator interface is designed to provide a user
friendly method of controlling, viewing menus, entering
settings and retrieving data from the relay. Five buttons
are provided for navigation around the menu structure.
LCD
A 4 line by 20 character liquid crystal display with power
save operation indicates the relay identifier, settings,
instrumentation, fault data and control commands.
Up to 6 user programmable general alarms can be
configured to display your own indications on the LCD.
LEDs
A green steadily illuminated LED indicates the ‘Protection
Healthy’ condition.
9 user programmable LEDs are available eliminating the
need for expensive panel mounted pilot lights and
associated wiring. Each LED is tri-color (red, green,
yellow) allowing for clear indication of the associated
function’s state and has a label insert for identification.
Relay Information
The device is identified by the rating label on the fascia.
The user can also give the device its own identity by
editing the ‘Relay Identifier’ displayed on the LCD or space
is provided to place a slip in label giving the relays
function.
Siemens Protection Devices Limited 7