Optional surge protection
Up to 2.5 kV (5 kA discharge current) of 8 µs rise time/20 µs
decay.
Output signal
Two-wire 4 to 20 mA dc, user-selectable for linear or square root
output, power of 3/2 or 5/2, 5th order or two 2nd order switching
point selectable programmable polynomial output.
HART
®
communication provides digital process variable (%,
mA or engineering units) superimposed on 4 to 20 mA signal,
with protocol based on Bell 202 FSK standard.
Output current limits (to NAMUR standard)
Overload condition
- Lower limit : 3.8 mA dc
- Upper limit : 20.8 mA dc
Transmitter failure mode (to NAMUR standard)
The output signal can be user-selected to a value of 3.6 or
21.6 mA on gross transmitter failure condition, detected by self-
diagnostics.
In case of CPU failure the output is driven <3.6 mA or >21.6 mA.
Profibus PA output
Power supply
The transmitter operates from 10.5 to 32 Vdc with no polarity.
For EEx ia approval power supply must not exceed 15 Vdc.
Intrinsic safety installation according to FISCO model.
Current consumption
- operating (quiescent) : 10.5 mA
- communicating : 20.5 mA
- fault current limiting : 16 mA max.
Output signal
Physical layer in compliance to IEC 1158-2/EN 61158-2 with
transmission to Manchester II modulation, at 31.25 kbit/sec.
Output interface
Profibus PA communication according to Profibus DP50170
Part 2/DIN 19245 part 1-3 compliant to Profiles 3.0 Class A & B
for pressure transmitter; ident. number 052B HEX.
Output update time : 25 ms
Function blocks
2 analog input, 1 transducer, 1 physical
Optional indicator
Integral display
- LCD : 4 digit characters, displaying process variable in
engineering units or as percentage value.
Display also indicates diagnostic messages.
Transmitter failure mode
On gross transmitter failure condition, detected by self-diagnos-
tics, the output signal can be driven to defined conditions,
selectable by the user as safe, last valid or calculated value.
FOUNDATION fieldbus output
Device type
Link Active Scheduler (LAS) capability implemented
Power supply
The transmitter operates from 9 to 32 Vdc with no polarity.
For EEx ia approval power supply must not exceed 24 Vdc.
Intrinsic safety installation according to FF application guide.
Current consumption
- operating (quiescent) : 10.5 mA
- communicating : 20.5 mA
- fault current limiting : 16 mA max.
Output signal
Physical layer in compliance to IEC 1158-2/EN 61158-2 with
transmission to Manchester II modulation, at 31.25 kbit/sec.
Function blocks/execution period
2 standard Analog Input blocks / 25 msec. max (each)
1 standard PID block / 70 msec. max.
Additional blocks
Transducer block, 1 standard Resource block,
1 custom Pressure with calibration block
Number of link objects : 25
Number of VCRs : 24
Output interface
FOUNDATION fieldbus digital communication protocol to
standard H1, compliant to specification V. 1.4; FF registration
IT011000.
Optional indicator
Integral display
- LCD : 4 digit characters, displaying process variable in
engineering units or as percentage value.
Display also indicates diagnostic messages.
Transmitter failure mode
The output signal is "frozen" to the last valid value on gross
transmitter failure condition, detected by self-diagnostics which
also indicate a BAD conditions. If electronic failure or short
circuit occur the transmitter consumption is electronically lim-
ited at a defined value (16 mA approx), for safety of the network.
PERFORMANCE SPECIFICATIONS
Stated at ambient temperature of 23°C ± 3K (75°F ± 5), relative
humidity of 50% ±20%, atmospheric pressure, mounting position
with vertical diaphragm and zero based range for transmitter with
seal isolating diaphragms in AISI 316 L ss and silicone oil fill and
HART digital trim values equal to 4-20 mA span end points, in linear
mode.
Unless otherwise specified, errors are quoted as % of span.
Some performance data are affected by the actual turndown (TD)
as ratio between Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER
SENSOR CODE PROVIDING THE TURNDOWN VALUE AS
LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE
CHARACTERISTICS.
Accuracy rating
% of calibrated span, including combined effects of terminal based
linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function block outscale range
- ± 0.10% for TD from 1:1 to 5:1
- ± 0.02 x for TD from 5:1 to 10:1
Multiply the values by 2 for sensor/seal combination marked (•)
URL
span