3
Sensor (URL) coefficient K5
The seal(s) constant time is calculated by the following formula
T
S6 (sec) = [K1 x (K2 + K3 x K4) x K5]
The total constant time of the transmitter/seal system is the
combination of relevant response times by the following
formula:
TTX (sec) = TTR + TS6) x 1.2] + 0.1
The following table details the transmitter time values (TTR) in
sec. for the transducers with specific filling fluids @25°C (77°F)
Sensor Code K5
0.4
0.2
A
B
Sensor Code
Silicone oil
DC 200
2
0.9
A
B
Inert
(Galden)
7.3
3.2
Silicone oil DC 200
Inert (Galden)
Fill Fluid K2
1
1.9
K3
0.12
0.37
Overpressure limits (without damage to the transmitter)
• Lower : 0.067 kPa abs, 0,67 mbar abs, 0.01 psia
(0.13 kPa abs, 1.33 mbar abs, 0.02 psia for sensor A).
Double the lower limit with inert filling.
• Upper (transmitter sensor limit or flange / fitting rating of
the seal, whichever is less)
- model 621EM
sensor code A : 1 MPa, 10 bar, 145 psi
sensor code B : 5 MPa, 50 bar, 725 psi
- flanged seals (S6F)
ANSI CL 150 : 2 MPa, 20 bar, 290 psi
ANSI CL 300 : 5 MPa, 50 bar, 725 psi
DIN ND 16 : 1.6 MPa, 16 bar, 230 psi
DIN ND 40 : 4 MPa, 40 bar, 580 psi
Static pressure
Transmitters model 621EM operate within specifications
between the following limits
• Lower
atmosphere (the two sides are wetted)
• Upper
same of overpressure limit
Proof pressure
The transmitter meets SAMA PMC 27.1 requirements and can
be exposed without leaking to line pressure of up to 10 MPa,
100 bar, 1450 psi (2 MPa, 20 bar, 290 psi for sensor A) or two
times the flange/fitting rating of the seal, whichever is less.
22
R(kΩ) =
Supply voltage - min. operating voltage (Vdc)
Load limitations - 4-20 mA and HART total loop resistance :
Optional indicators
• Output meter (user adjustable)
- LCD : 3 1/2-digit with 10 mm (3/8 in) high, 7-segment
characters. Engineering unit labels are provided. LCD
output meter may be calibrated within the range -1999 to +
1999 with a span adjustable between 100 and 3998 units.
(Display of decimal point, if required, is switch selectable)
- analog : 36 mm (1.4 in) scale on 90°
• Integral display
- LCD: 4-digit with 8 mm. (5/16 in) high, 9-segment alphanu-
meric characters.
User-definable display mode with HART communication :
- process variable in engineering units, or
- percent of range, or
- process variable in engineering units and percent of range
alternating every 3 seconds, or
- process variable in engineering units and digital
output (4 to 20 mA) alternating every 3 seconds.
Factory selectable display mode with 4 to 20 mA output :
- percent of range
- percent of range and 4 to 20 mA output alternating every
3 seconds
Display also indicates diagnostic messages.
• CoMeter
- 5-digit (± 99999 counts) programmable with 7.6 mm. high (3 in),
7-segment numeric characters plus sign and digital point
- 10-segment bargraph display (10% per segment)
- 7-digit LCD with 6 mm. high (2.3 in), 14-segment alphanumeric
characters.
ELECTRICAL CHARACTERISTICS AND OPTIONS
• HART digital communication and 4 to 20 mA output
Power Supply
The transmitter operates from 10.5 to 42 Vdc with no load and
is protected against reverse polarity connection (additional load
allows operations over 42 Vdc).
For EEx ia and intrinsically safe (FM, CSA and SAA) approval
power supply must not exceed 30 Vdc.
Filling coefficient (K2 and K3)
Operating temperature coefficient (K4)
to be considered only for operating temperature less than
25°C (77°F)
K4 = T - 25 (absolute value)
Coefficient K4 should be considered = 0 for temperatures
above 25°C (77°F)
(volts)
MINIMUM OPERATING VOLTAGES
10.5
with integral display
with optional output analog indicator
with optional surge protection
with optional output LCD indicator
with optional output LCD indicator and surge protection
10.7 12.1 12.5 14.1
no link on output indicator plugs
14.3
with CoMeter
13.3
Supply voltage
Total loop resistance
250
(ohms)
1430
25 (ref.)10.5 (volts)42
4 to 20 mA only
4 to 20 mA and
HART digital communication
600