Manual – MOVITOOLS® - Connection to SIMATIC S7 via Ethernet
3
Function blocks and data blocks in the PLC
PLC Configuration in STEP7
3.2 Function blocks and data blocks in the PLC
You will need different function blocks and data blocks (depending on the PLC you use)
for operating MOVITOOLS
®
via SIMATIC S7 Ethernet.
Hardware data
block
A hardware data block (HDB) assigns the logical I/O address of the inverter to the dis-
played PROFIBUS address for MOVITOOLS
®
via SIMATIC S7 Ethernet. There are two-
dimensional arrays and a header string (→ following figure) in this hardware data block.
You can view and alter the values of the arrays in the menu item [View] / [Declaration
View.]
• HeaderString
The string is necessary for clear identification of the "SMLP server_vx.xx" function
block and may not be altered.
• IdentString
You can save a string of up to 24 characters to enter a user-specific identification in
the PLC. Use MOVITOOLS
®
to retrieve this ID.
• HwCfg_LAddr
Two-dimensional array with Index 1 (values 1 ... 3 are possible) mapping the DP sub-
net and index 2 (values 0 ... 125 are possible) describing the PROFIBUS address in
the respective subnet. The value of the respective array word corresponds to the log-
ical I/O address of the SEW unit. The value "0xFFFF" is a placeholder for non-estab-
lished units and may not be used in assigning the logical I/O addresses in the STEP7
hardware configuration for SEW units.
• HwCfg_DevType
Two-dimensional array with Index 1 (values 1 ... 3 are possible) mapping the DP sub-
net and Index 2 (values "TRUE" or "FALSE") describing the PROFIBUS address in
the respective subnet. The value of the respective array bool determines if a device
is addressed via the DP-V1 channel or the parameter channel saved in the cyclical
data. If the value is "True", then parameters will be set via the DP-V1 channel (logical
I/O address of PD data). If the value is "False," then parameters will be set via the
DP channel (has to be set up in the STEP7 hardware configuration; the logical I/O
address of the parameter channel in the cyclical data).
11168AXX