12 Texas Instruments Communication Driver Manual
Memory Ranges for the 405 Series Driver
The 405 Series driver supports the following memory types and ranges.
Memory Type Memory Address V Memory Addresses
16-Bit Word
Timer TMR0-TMR177 V00000-V00177
Counter CNT0-CNT177 V01000-V01177
User Data V01400-V07377 V01400-V07377
System Param V07400-V07777 V07400-V07777
Memory Type Memory Address V Memory Addresses
Byte or Bit
Remote I/O GX0-GX777 V40000-V40037
Inputs X0-X477 V40400-V40423
Outputs Y0-Y477 V40500-V40523
Control Relays C0-C737 V40600-V40635
Stages S0-S577 V41000-V41027
Timer Relays T0-T177 (Read Only) V41100-V41107 (Read Only)
Counter Relays CT0-CT177 (Read Only) V41140-V41147 (Read Only)
Special Relays SP0-SP137 (Read Only) V41200-V41205 (Read Only)
Special Relays SP320-SP617 (Read Only) V41215-V41230 (Read Only)