Vista de pagina 83
2000591-001 Troubleshooting 79
DataNET Troubleshooting Guide
If an ANG-DN and a DataNET Hub fail to establish a link, this may be
due to one of two situations:
a configuration conflict,
a link signal quality problem.
If after connecting an ANG_DN port the DNETB Green LED never
comes on, or intermittently flashes between green and red, there may be
a configuration conflict. Configuration conflicts can be caused by cabling
or improper software configuration parameters.
Verify that the Channel A DataNET link is connected to the A Hub half
and that the Channel B DataNET link is connected to the B Hub half.
Verify that both Channels A & B utilize the same port number on their
respective Hub half. Then display the Port Status screen by connecting a
PC to the Configuration Port, logging in, and typing display links. Verify
that the two Ports are connected as expected.
The following example shows that port #1 (ANG_DN Channel A board) is
connected to the ADH Channel. Port#2 (ANG_DN Channel A board) is
also connected to the DataNET Channel A Hub. Note that the Ethernet
cross-link status is Online.
local> display links
Port: Medium: Status: Connected to:
1 ADH Copper Connected ADH Channel A
2 DN Copper Connected DN Channel A
Ethernet Online
Improper cable impedance matching. Verify that the impedance jumpers
located on J2 are set to match the attached cable impedance. The avail-
able selections are for 100, 120, and 150 Ohms.
Cable Shielding problems. Make sure the cable is of the recommended
type and that the twisted-pair shield is grounded at one end only. (Hub
end recommended.)
Instructions
Configuration
Conflicts
Cable Connected to
Wrong Hub or Port
Example
Cable Impedance
Matching
Cable Shielding
Vista de pagina 83