4-14
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
In certain cases the station number in the EEPROM of the DP/ASi link has to
be reset. Proceed in the following order:
Step
Action
1 Turn off the power supply for the DP/ASi link.
2 Turn switch 8 on the DIP switch block to OFF.
3 Turn on the power supply for the DP/ASi link and then turn it off
after automatic start-up of the DP/ASi link. Start-up is aborted
with an error message. The station number is reset to 126.
4 Turn switch 8 on the DIP switch block to ON.
5 Turn on the power supply for the DP/ASi link.
6 Set the correct station number again with the ET 200 Handheld or
by means of the DP master.
Resetting station
numbers
Installing and Wiring the DP/ASi Link