Parameters/address space
4.3 Declaration of parameters
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
19
Smoothing
The individual measured values are smoothed using filtering. The smoothing can be set in 4
levels.
Smoothing time = number of module cycles (k) x cycle time of the module.
The following figure shows after how many module cycles the smoothed analog value is
almost 100%, depending on the set smoothing. Is valid for each signal change at the analog
input.
None (k = 1)
Weak (k = 4)
Medium (k = 16)
Strong (k = 32)
Figure 4-1 Smoothing with AI 8xU/I HS
Hardware interrupt 1 or 2
Enable a hardware interrupt at violation of high limit 1 or 2 or low limit 1 or 2.
Low limit 1 or 2
Specifies the low limit threshold that triggers hardware interrupt 1 or 2.
High limit 1 or 2
Specifies the high limit threshold that triggers hardware interrupt 1 or 2.