Table 4: Metasys Integrator Unit Setup for Siemens MODBUS
Applications
Vendor Communication Table (.VCT File)
Model 9300 Power Meter
SI_9300m.VCT
Model 9500/9600 Power Meter
SI_9500m.VCT
Port Setup
Baud Rate
9600
Word Length
8
Stop Bit
1
Parity
None
Interface
RS-485
Network Setup
Vendor Address
0-255
Timeout Value
1000 ms
Poll Delay
Model 9300 Power Meter
Model 9500/9600 Power Meter
55 ms
55 ms
Performance Guide
Approximate Scan Time for a Single
N2 Address
Model 9300 Power Meter
Model 9500/9600 Power Meter
2 seconds
2 seconds
12 Metasys Integrator—Metasys Integrator Siemens Application