Siemens Building Technologies
Cerberus Division
Mode Detector test
cont.
Poll test alarms in the event memory
1. Press
F2
Ü The MAIN MENU is displayed
Press to select DEVICE level
2. Press
ok
Ü The STATIONS overview is displayed
Press
to select the desired STATION
3. Press
F1
Ü The function list Control unit is displayed
Press
to select poll EVENT MEMORY
4. Press
ok
Ü The function list Event Memory is displayed
Press to select poll all TEST ALARM
messages
5. Press
ok
Ü The TEST Alarms are displayed
use
and to poll the test alarms
MAIN MENU
FIRE detection
EXTINGUISHING sections
CONTROL in- /outputs
GEOGRAPHICAL location
DEVICE level
logical address (CSX no.)
ok:select F1:function C:end
STATIONS
01 CC1142 CBUS no1
02 CI1142 CBUS no2
05 CT1142 CBUS no5
ok:funct.unit F2:menu F1:function
poll INFORMATION terminal
set contrast of DISPLAY
FUNCTION LIST terminal:
set sound level of BUZZER
poll EVENT MEMORY terminal
initiate LAMP TEST
ISOLATE PRINTER terminal
ok:execute F2:stations c:end
poll all INFORMATION messages
ok:execute F1:station F2:->date/time
FUNCTION LIST event memory:
poll all messages
poll all DANGER messages
poll all DISCONNECTION messages
poll all TEST-ALARM messages
poll all FAULT messages
^/v:scroll F1:print F2:->date/time
EVENT MEMORY
**** TOP OF LIST ****
03-SEPT-1997 16:15:52 INFORMATION
+detector TEST ACTIVATION
main building / 1st floor
room 102
04-SEPT-1997 09:00:59 INFORMATION