NIM Primitives
4-49
SIMATIC TIWAY I Series 500 NIM User Manual
The first request also contains the between response to request time-out
value. This value corresponds to the number of seconds that the attached
device will wait for the next upload request. If the time expires, the
attached device will exit upload mode. The first response also returns the
actual time-out value that will be used, since some attached devices may
support a maximum time-out value less than the value requested.
Upload Request Parameter Descriptions. The basic format of the
request is as follows:
LLLL 58 XX
LLLL 58 00 RRRR MMMM OOOO
LLLL 58 01 RRRR YYYY DD ... DD
LLLL 58 02 RRRR
LLLL 58 03 RRRR
where:
Symbol Value Definition
CC
00 Initial upload request
01 Next block upload request
02 End upload request acknowledge
03 Abort upload operation
YYYY (number) Requested block sequence number starting with 0
(present when CC = 1)
RRRR (number) Host defined reference field returned with response
MMMM (binary) Upload configuration bit map present only when
CC = 0. A1 in a bit position indicates that the
corresponding segment will be included in the upload.
The chart below illustrates this concept.
OOOO (number) Time-out value in one second increments (present only
when CC = 0)
 
 


 