IEC 1131-3 Instructions
10-12
S7-200 Programmable Controller System Manual
C79000-G7076-C233-01
Off-Delay Timer
The Off-Delay Timer function block is used to delay the
setting of an output false for a fixed period of time after
the input goes false. It times up to the preset value when
the enabling input (IN) goes false. When the elapsed
time (ET) is greater than or equal to the preset time (PT),
the timer output bit (Q) turns on.
Once the preset is reached, the timer output bit turns false and the elapsed time is
maintained until the enabling input (IN) makes the transition to true. If the enabling
input (IN) makes the transition to false for a period of time shorter than the preset
time (PT), the output bit remains true.
For information about timer numbers and resolutions, refer to Table 10-3.
Inputs/Outputs Operands Data Types
IN (LAD) Power Flow BOOL
IN (FBD) I, Q, M, SM,T, C, V, S, L, Power Flow BOOL
PT (LAD & FBD) VW, IW, QW, MW, SMW, LW, SW, AIW, AC, Constant, *VD, *AC, *LD INT
Q (LAD & FBD) I, Q, M, SM, V, S, L BOOL
ET (LAD & FBD) VW, IW, QW, MW, SMW, LW, SW, AQW, AC,*VD, *AC, *LD INT
xxx refer to Table 10-3 TOF
Pulse Timer
The Pulse Timer function block is used to generate
pulses for a specific duration. As the enabling input (IN)
becomes true, the output bit (Q) turns on. The output bit
remains true for the pulse specified within the preset time
(PT). Once the elapsed time (ET) reaches preset (PT),
the output bit (Q) becomes false.
For information about timer numbers and resolutions, refer to Table 10-3.
Inputs/Outputs Operands Data Types
IN LAD) Power Flow BOOL
IN (FBD) I, Q, M, SM, T, C, V, S, L, Power Flow BOOL
PT (LAD & FBD) VW, IW, QW, MW, SMW, LW, SW, AIW, AC, Constant, *VD, *AC, *LD INT
Q (LAD & FBD) I, Q, M, SM, S, V, L BOOL
ET (LAD & FBD) VW, IW, QW, MW, SW, LW, AQW, AC, *VD, *AC, *LD INT
xxx refer to Table 10-3 TP
L
A
D
TOF
IN
xxx
F
B
D
Q
ET
222 224
333
221
PT
L
A
D
TP
IN
xxx
F
B
D
PT
Q
ET
222 224
333
221