Version 091708
Remote relay state control via communications
Failsafe operation on measurement loss, including independent mA
output and relay operation configuration.
Digital Communications
The level controller shall:
Store data related to the digitized echo profiles, distance calculation,
signal processing functions, process control functions, and system
configuration.
Map stored data to Modbus type read/write and read only registers, as
defined by the level controller supplier.
Provide access to stored data via:
RS232 port with RJ-11 connector for use with SIMATIC PDM.
RS-485 port with screw terminals for external connection to the RS-485
modem or any compatible RS-485 communications network.
SmartLinx port for use with an interchangeable SmartLinx card for direct
connection to the corresponding industrial bus protocol.
User Interface
The level controller shall enable user access to read only and read/write enabled
data, using any of the following methods:
Direct or scroll access to data stored in numerical parameters,
using the hand programmer and graphic LCD display.
IBM PC compatible computer access to data and digital echo
profiles, using the SIMATIC PDM instrument configuration
package.
HMI, SCADA, PLC, or DCS system access to data stored in
Modbus registers via digital communications.
Transducer Functions
Acoustic / Electrical Energy Conversion
The transducer shall employ a piezzo electric driver element to convert the
electrical excitation supplied by the level controller, to acoustic energy radiated
axially and perpendicular from the transducer face. The piezzo electric driver
shall also convert acoustic excitation to an electrical signal for processing by the
level controller.
Integral Temperature Sensor
The transducer shall also employ an internal temperature sensor that shall
provide a signal to the level controller representing the temperature measured at
the transducer face.