For Operation in the Control Cabinet
SIRIUS 3RA6 Compact Starters
Infeed systems for 3RA6
6/53
SIRIUS Innovations Supplement 2011
6
$
Infeed
The 3-phase infeed is available as an infeed with screw connec-
tion (4-2 AWG up to 63 A or 0-2/0 AWG up to 100 A) and a an
infeed with spring-type connection (4-2 AWG up to 63 A).
The infeed with spring-type terminal can be attached to the left
side, as well as the right side, of an expansion module.
The screw terminal infeeds are permanently fitted to the left side
of a 3-socket expansion module.
The infeeds with screw connection enable connection of the
main conductors (L1, L2, L3) either from above or from below.
The infeeds with screw connection come packaged with 1 end
cover, while the infeed with spring-type connection comes pack-
aged with 2 end covers.
%
Three-socket expansion modules
The expansion module with 3 sockets for compact starters is
available with screw connection and with spring-type
connection.
Expansion modules enable the infeed system to be expanded
and can be connected to each other in any number up to a max-
imum length of 1.2 meters.
Two expansion modules are held together with the help of
2 connecting plates and 1 expansion plug. These assembly
parts are included in the scope of supply of the respective
expansion module.
When the infeed system for 3RA6 compact starters is used, the
compact starters (plug-in modules) are easily mounted and re-
moved even when live.
Optional possibilities:
PE connection on motor starter side
Outfeed for external auxiliary devices
Connection to 3RV19 or 3RV29 infeed system
Integration of SIRIUS 3RV1 motor starter protectors size S0
(using 3RA68 90-0BA adapter)
&
Two-socket expansion modules
If only 2 instead of 3 additional sockets are required, then the
2-socket expansion module is the right choice. It has the same
functionality as the 3-socket expansion module.
(
Expansion plug
Two expansion modules can be connected together using the
expansion plug. Flexible expansion of the infeed system is thus
possible.
)
PE infeeds
This module enables a PE cable to be connected.
The PE infeed can be ordered with screw connection and
spring-type connection (2 AWG) and can be fitted on the right or
left to the expansion block.
*
PE expansion plug
The PE expansion plug is inserted from below and enables two
PE bars to be connected.
+
PE tap-off
The PE tap-off is available with screw connection and spring-
type connection (10-8 AWG). It is snapped into the infeed sys-
tem from below.
,
Connecting plates
Two connecting plates are used to hold together 2 adjacent
expansion modules.
-
End covers
On the last expansion module of a row, the slot provided for the
expansion plug can be covered by inserting the end cover.
.
45 mm adapters for SIRIUS 3RV1 motor starter protectors
SIRIUS 3RV1 motor starter protectors size
S0 with screw connec-
tion can be fitted to the adapter, enabling them to be plugged
into the infeed system.
Terminal blocks
Using the terminal block, three phase power can be fed out of
the infeed system; this means that single-phase, two-phase and
three-phase components can also be integrated in the system.
If the end cover is removed, the terminal block can be inserted
into an expansion module.
Expansion plug for SIRIUS 3RV19 infeed systems
If the end cover is removed, the expansion plug for the SIRIUS
3RV19 infeed system can be inserted into an expansion module.
It connects the infeed system for 3RA6 compact starters with the
SIRIUS 3RV19 infeed system.
Maximum rated operational current
The following maximum rated operational currents apply for the
components of the infeed system for 3RA6:
When several expansion modules are mounted side by side, the
maximum rated operational current from the 2nd expansion
module to the end of the row is 63 A.
Proposal for upstream short-circuit protection devices
The following short-circuit data apply for the components of the
infeed system for 3RA6 compact starters:
1)
To prevent the possibility of short-circuits, the cables on the terminal block
must be installed so that they are short-circuit proof according to
EN 60439-1 Section 7.5.5.1.2.
Component Maximum rated
operational current
A
Infeed with screw connection 0-2/0 AWG 100
Infeed with screw connection 4-2 AWG 63
Infeed with spring-type connection 4-2 AWG 63
Expansion plugs 63
Conductor
cross-
section
Inscriptions Proposal for
upstream short-circuit
protection device
AWG
Short-circuit protection for
infeed block (4-2 AWG)
with screw connection
14-2 I
d, max
= 19 kA, I²t = 440 kA²s 3RV10 41-4JA10
Short-circuit protection for
infeed block (0-2/0 AWG)
with screw connection
14-2/0 I
d, max
= approx. 22 kA 3RV10 41-4MA10
Short-circuit protection for infeed block
with spring-type connection
12 I
d, max
= 9.5 kA, I²t = 85 kA²s 3RV10 21-4DA10
10 I
d, max
= 12.5 kA, I²t = 140 kA²s 3RV10 31-4EA10
8 I
d, max
= 15 kA, I²t = 180 kA²s 3RV10 31-4HA10
6-4 I
d, max
= 19 kA, I²t = 440 kA²s 3RV10 41-4JA10
Short-circuit protection for terminal block
16 I
d, max
= 7.5 kA 5SY...
14 I
d, max
= 9.5 kA
1)
12 I
d, max
= 9.5 kA
10 I
d, max
= 12.5 kA
© Siemens AG 2011