Alarm and fault messages
4.2 Alarm and fault messages
31
Table 4-3 Fault 0
(Alarm) General fault on transformer
Condition
The hardware contact in the power unit has tripped.
Causes
There is a defect in the inverter.
Measures
Replace the affected components.
Replace the drive.
Table 4-4 Faults 1 and 33
Message 1 (alarm): Inverter is signaling overtemperature, stage 1
Fault 33 (alarm): Inverter is signaling overtemperature, stage 2
Condition
An excessive heatsink temperature in the inverter has
been detected.
The thermoclick circuit for the reactors and transformers
has been interrupted.
Cooling system is not working properly
o Drive fan is not running
Fan motor is defective
Start capacitor is defective
No power supply to fan
USI is defective
Infeed transformer is defective
o Heatsink is blocked
o Drive fan speed is too low
Infeed transformer is connected to tap
460 V instead of 400 V
Heat generation is exceeding tolerance
o Current is too high
Parameter setting error (CU software –
current limit value)
o IGBT module defective
Fault in measured-value sensing
o Temperature sensor in heatsink is defective
o Temperature sensor connection is defective
o CU data input is defective
Causes
Reactor or transformer is overheating (fault 33 only,
without preceding warning level 1 in the PPsolar
event memory)
o Cooling system is not working properly
Housing fans are not running
Fans are defective
Thermostat is defective
Thermostat is incorrectly set
Air intake is restricted
Air inlet grille on housing is clogged
up
Air outlet is restricted
Vista de pagina 30