Technical Instructions GGD Electronic Damper Actuator Designed for UL Listed Fire/Smoke Control Dampers
Document No. 152-046P25
January 9, 2008
Page 2 of 4 Siemens Building Technologies, Inc.
Specifications
Power supply
Operating voltage 24 Vac ±20%
115 Vac ±15%
230 Vac ±10%
Frequency 50/60 Hz
Power consumption
running 150 VA
holding 10 VA
Function
Running torque 142 lb-in (16 Nm)
Spring return torque 108 lb-in (12 Nm)
Minimum stall torque 350 lb-in (39 Nm)
Torque reduction at elevated temperature Less than 10%
Runtime for 90°
operating with motor at 60 Hz 15 seconds nominal
closing (on power loss) with spring return 15 seconds maximum
Nominal angle of rotation 95°
Life Expectancy
Minimum 35,000 full stroke cycles.
Mounting
Damper shaft size
Standard 3/8 to 1 inch (8 to 25.6 mm)
Oversize 1.05 inch maximum (26.6 mm)
Minimum shaft length 3/4-inch (20 mm)
Housing
Enclosure NEMA 1
Material Die cast aluminum alloy
Ambient conditions
Ambient temperature
operation 0 to 130°F (-18 to 55°C)
One time 350°F (177 °C)
for 1/2 hour (per UL555S)
storage and transport -25 to 158°F (-32 to 70°C)
Ambient humidity (non-condensing) Maximum 95% R.H.
Agency certification
UL listed to UL873
cUL certified to Canadian standard
C22.2 No. 24-93
Australian EMC Framework (C-tick)
with the limits per
AS/NZS 2064 1/2:1997
Miscellaneous
Pre-cabled connection 18 AWG
Dimensions See Figure 1.
Weight ≈7 lbs. (3.2 kg)
Eight pack ≈56 lbs. (25.4 kg)
Warning/Caution Notations
WARNING
Personal injury/loss of life may occur if you do
not perform a procedure as specified.
CAUTION:
Equipment damage may occur if you do not
follow a procedure as specified.